| 1) Accuracy level: XSE-D level 0.05, XSE-T level 0.1 2) Output voltage: A) 3 x 100V/57.7VY: 3 x 100V B) 3 x 380V/220VY: 3 x 380V C) Regulating scope: 0-120% consecutively adjustable D) Regulating fineness: Better than 0.01% E) Special voltage range can be setup according to users' orders 3) Current range: 0.1A, 0.25A, 0.5A, 1A, 2.5A, 5A, 10A, 20A, 50A, 100A A) Regulating scope: 0-120% consecutively adjustable B) Regulating fineness: Better than 0.01% 4) Output power: A) Voltage loop: XSE-16 200VA B) Current loop: XSE-16 350VA 5) Stability of output voltage, current and power: A) ¡0.02%/120S: PF=1 (level 0.05 type) B) ¡0.05%/120S: PF=1 (level 0.1 type) 6) Wave distortion of output voltage and current: ¡0.5% 7) Symmetry of three phase: Better than 120 + 0.3 8) Frequency range: 45 - 65Hz, regulating fineness 0.1Hz 9) Phase shifting range: -180.0 ~ 180.0, regulating fineness 0.1 10) Standard crystal oscillator stability: ¡10-7/s 11) Indicating instruments class: A) Voltmeter and ammeter accuracy: Level +0.5% B) Phase meter accuracy: +1 C) Cymometer accuracy: +0.1Hz 12) Maximum meters for test: 10, 16 13) Power supply: 3 x 220 + 10%~50Hz 14) Maximum power consumption: XSE-16 4, 000VA 15) Working environment: A) Temperature: 20 + 5 C B) Relative humidity: ¡85% 16) Dimensions and weight (XSE-16): 2, 380 x 720 x 1, 870mm, 400kg |